Alarm ID Alarm
Name
Severity Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
21 Lithium
battery low
temperatur
e protection
Minor The cell
temperatur
e rises
above the
protection
threshold.
Charge
low
temperat
ure
protectio
n: The
minimu
m cell
temperat
ure is
less than
0°C.
Discharg
e low
temperat
ure
protectio
n: The
minimu
m cell
temperat
ure is
less than
–20°C.
The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Possible
cause: The
ambient
temperatur
e of the
lithium
battery is
too low or
the heater
cannot
work
properly.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.