Alarm ID Alarm
Name
Severity Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
53 Timeout in
approachin
g rated
output
voltage
during
startup
Critical You need to
manually
rectify the
fault or
power o
and restart
the device.
The inverter
voltage is
not soft-
started to
the rated
output
voltage
within 10s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
55 Excessive
DC
component
Critical The alarm
can be
automatical
ly cleared
for three
times. After
that, you
need to
manually
clear the
fault or
power
o
and restart
the device.
The DC
component
of the
output
voltage is
greater
than 200
mV for 20s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
Possible
cause:
The half-
wave
load
power is
too high.
Measure:
Locate the
load and
remove it.
Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
57
Current
sensor fault
Critical You need to
manually
rectify the
fault or
power o
and restart
the device.
In power-on
mode, the
current
sampling
deviation
exceeds
10% of the
total
sampling
range.
The system
cannot start
the inverter
and directly
delivers
output in
bypass
mode.
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
UPS2000-G-6KRTLL
User Manual 4 Control Panel
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 86