UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
5 Operations
Copyright © Huawei Technologies Co., Ltd.
155
Commission the voltages on other power uints one by one.
Step 7 (Opinion) If a BCB box is configured, choose Settings > Dry Contacts and set OL for
detecting BCB connection and STA for detecting battery circuit breaker status to Enabled.
Figure 5-5 BCB connection setting
Step 8 Turn on the external output switch to supply power to loads.
----End
5.2 Shutting Down and Powering Off the UPS
Context
If you need to shut down the inverter to transfer the UPS to bypass mode, perform only
Step 1 after confirming that the UPS generates no alarm.
If you need to power off the UPS, perform all the preceding steps.
After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power. Before you shut down the UPS, ensure
that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Shut down the inverter on the LCD.
On the main menu, choose Control. On the login screen, enter a password.
Click Inv. OFF, press to shut down the inverter, as shown in Figure 5-6.