UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
8 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
> 0.99 (full load); > 0.98 (50% load)
8.6 Bypass Input Electrical Specifications
Three-phase, four-wire, and PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input use different power sources or
share a power source.
8.7 Battery Specifications
360–528 V DC (12 V batteries, 30–44 batteries, 32 by default); If
there are 36–44 batteries, output power is not derated. If there are
30 batteries, output power is derated to 0.94.
Intelligent battery management
In the case of mains outage, batteries start the UPS, which supplies
power to loads.
No battery string is shared by default. Battery string sharing is
supported in a parallel system.
Equalized voltage: 2.3–2.4 V/Cell, default: 2.35 V/Cell (30–42
batteries)
Equalized voltage: 2.3–2.35 V/Cell, default: 2.35 V/Cell (44
batteries)
Float voltage: 2.23–2.3 V/Cell, default: 2.25 V/Cell (30–44
batteries)