UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
8 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
180
Item
30 kVA
40 kVA
80 kVA
Rated frequency
50 Hz/60 Hz
Input frequency
4070 Hz
Input PF
> 0.99 (full load); > 0.98 (50% load)
THDi
< 3% (linear load)
8.6 Bypass Input Electrical Specifications
Item
30 kVA
40 kVA
80 kVA
Input system
Three-phase, four-wire, and PE wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Rated frequency
50 Hz/60 Hz
Frequency range
±6 Hz (adjustable, 0.56 Hz, ±2 Hz by default)
Input mode
The mains input and bypass input use different power sources or
share a power source.
8.7 Battery Specifications
Item
30 kVA
40 kVA
80 kVA
Battery voltage
360528 V DC (12 V batteries, 3044 batteries, 32 by default); If
there are 3644 batteries, output power is not derated. If there are
30 batteries, output power is derated to 0.94.
Battery management
Intelligent battery management
One-button cold-start
In the case of mains outage, batteries start the UPS, which supplies
power to loads.
Battery string sharing
No battery string is shared by default. Battery string sharing is
supported in a parallel system.
Charge voltage
Equalized voltage: 2.32.4 V/Cell, default: 2.35 V/Cell (3042
batteries)
Equalized voltage: 2.32.35 V/Cell, default: 2.35 V/Cell (44
batteries)
Float voltage: 2.232.3 V/Cell, default: 2.25 V/Cell (3044
batteries)