UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
3 Installation
Copyright © Huawei Technologies Co., Ltd.
35
Reserve a clearance of at least 800 mm on the front of the cabinet.
Reserve a clearance of at least 300 mm on the top of the cabinet.
Keep a clearance of at least 300 mm at the rear of the cabinet. If you need to perform
operations at the rear of the cabinet, keep a clearance of at least 800 mm.
Figure 3-3 takes the UPS5000-A-30 kVA/40 kVA as an example to show the installation
clearance.
Figure 3-3 Installation clearances (unit: mm)
3.1.2 Tools and Instruments
Insulate installation tools to prevent electric shocks.
Prepare the following tools and meters indicated in Table 3-1 for installation.
Table 3-1 Tools and meters
Tools and Meters
Electric pallet truck
Manual pallet truck
Ladder
Rubber mallet