UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
3 Installation
Copyright © Huawei Technologies Co., Ltd.
42
UPS
Capacity
Component
Specifications
Manufacturer
40 kVA
Mains input
circuit
breaker
T1N160 TMD R100 FFC 3P
Bypass input
circuit
breaker
T1N160 TMD R100 FFC 3P
80 kVA
Mains input
circuit
breaker
T1N160 TMD R160 3P FFC
Bypass input
circuit
breaker
T1N160 TMD R160 3P FFC
30 kVA
Output
branch circuit
breaker
S203 C50
ABB (recommended when
the short-circuit current of
the circuit breaker is
located is less than 6 kA.)
40 kVA
S203 C63
80 kVA
T1N160 TMD R125 3P FFC
ABB (recommended when
the short-circuit current of
the circuit breaker is
located is less than 36 kA.)
The input front-end and output back-end circuit breakers recommended in Table 3-7 are for
reference only.
If multiple loads are connected, branch circuit breaker specifications must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.
3.1.4 Unpacking and Checking