The neutral terminals of the UPS5000-A-80 kVA are near the interior of the cabinet. It is recommended
to connect the neutral cable before other power cables.
----End
3.2.7.4 Connecting AC Output Power Cables
After you connect output power cables, if loads are not ready to be powered, insulate the end
of the system output power cable.
Connect AC output power cables to output terminals N, U, V, and W on the UPS cabinet, as
shown in Figure 3-60 and Figure 3-61.
Figure 3-60 Connecting AC output power cables to the UPS5000-A-30 kVA/40 kVA