3.2.8 Remote EPO
Huawei does not provide the EPO switch or cable. Prepare them by yourself. The
recommended cable is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and cover the
cable with protective tubing.
Triggering EPO will shut down the rectifier, inverter, charger, and static bypass, but does
not disconnect the UPS mains input. To power off the UPS completely, turn off the
front-end input switch when you trigger EPO.
Connect the EPO switch to specified dry contacts on the UPS. Figure 3-65 uses the
UPS5000-A-30 kVA/40 kVA UPS as an example.
By default, the EPO switch is NO. When you turn on the EPO switch, EPO is triggered.