30
Remarks:
1. In heating mode, if the water out temperature is higher than the set temperature over 7 , LED controller
displays EE04 for water over-heating protection.
2. In cooling mode, if the water out temperature is lower than the set temperature over 7 , LED controller displays
PP11 for water over-cooling protection.
For example below:
Mode
Water out
temperature
Setting
temperature
Condition Malfunction
Heating mode 36 29 Tout - Tset
7
EE04
Overheating protection for water
temperature (T2)
Cooling mode 23 30 Tset - Tout
7
PP11
Too low protection for water
temperature (T2)
T
SET Temp.
+7
T
SET Temp.
+5
Frequency Decrease
EE04 Water Overheating Protection
PP11 Water Overcooling Protection
Compressor Stop and EE04 displays
T water out
Normal Operation
T water out
T
SET Temp.
-7
T
SET Temp.
-5
Normal Operation
Frequency Decrease
Compressor Stop and PP11 displays