17
Sl.No Parameter Address Resolution
LT HT
1 R - Voltage 40001 0.1 0.01
2 Y - Voltage 40002 0.1 0.01
3 B - Voltage 40003 0.1 0.01
4 RY Voltage 40004 0.1 0.01
5 YB Voltage 40005 0.1 0.01
6 BR Voltage 40006 0.1 0.01
7 R Current 40007 0.1 0.1
8 Y Current 40008 0.1 0.1
9 B Current 40009 0.1 0.1
10 kVA 40010 0.1 1
11 kW 40011 0.1 1
12 kVAr 40012 0.1 1
13 PF 40013 0.001 0.001
14 Frequency 40014 0.01 0.01
15 kWH MSB 40015 0.1 1
16 kWH LSB 40016 0.1 1
17 Meter Type / Runhour MSB 40017
18 Runhour LSB 40018
19 Import / Export 40019
The address of the parameters are as follows.
Note:
a) PF Calculation : If P.F < 1000 PF is in Lag (P.F = PF)
If P.F > 1000 PF is in Lead P.F = (PF-1000)
b) kWh Calculation : kWh = (kWh MSB * 65536) + kWH LSB
c) Meter Type / Runhour MSB : 256
d) Q = Meter Type : 03 = LT 3W, 04 = LT 2W, 05 = HT 3W,
06 = HT 2W
e) Imp. & Exp. status : 0 = Import, 1 = Export
f) R : Runhour MSB
g) Total Runhour : (Runhour MSB * 65536 ) + Runhour LSB