EasyManuals Logo

ICM Controls ICM455 User Manual

ICM Controls ICM455
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
ICM455
Important Safety Information
HIGH VOLTAGE WARNING!
– Turn off power at the
main service panel before installing.
Programmable,
Three-Phase
Voltage Monitor
Phase Unbalance Protection
Voltage Unbalance: 2-20%, adjustable
Over/Under Voltage
Under Voltage: 2-25%, adjustable
Over Voltage: 2-25%, adjustable
Phase Loss Protection
Phase Loss Condition: Equals 25% of nominal for any given phase; system will
shut down and a fault will be recorded if this should occur.
Delay on Break Timer
Control Voltage: 18-240 VAC
Time Delay: 15 seconds to 10 minutes
Fault Interrogation Delay
Time Delay: 0 – 15 seconds, adjustable
Provides a delay between fault detection and system shutdown—helps to eliminate
nuisance trips and unnecessary shutdowns.
Parameters
Installation
1.Turnoffpoweratmainservicepanel.
2.Usingtwo(2)#8screws,mounttheICM455inacool,dry,easilyaccessible
locationinthecontrolpanel.
3.Connectvoltageasshownin“WiringDiagram”.Leaveexistinglineandloadside
connectionsintactonthecontactor.
4.Loadsidemonitoringisoptional(unitmaybeusedtomonitorlinesideonly).Wire
thecontactorandoptionalcontrolvoltagemonitorasshownin“SystemDiagram”.
Note:Load/line wire must be rated for 3-phase voltage rating, 20ga minimum.
5.Uponapplicationofpower,theICM455willbeonlineandwillbegintomonitor
thesystem.
Note: If voltage is not correct, see “Voltage Read Calibration” in Button
Functions section
• Terminals3and4arethecontrolsignalinputterminals.
• “ControlMode”isturnedONorOFFinsetup.
• With“ControlMode”settoON,theremustbeavoltagepresentonterminals3
and4fortherelayoutputterminals1and3toclose;thisvoltagecanbesupplied
fromathermostat,pressureswitch,etc.
• Whenthevoltageonthesesterminalsisre-applied,theunitwillnotre-energize
untilthedelayonbreak(0-10minutes)timehaselapsed.
• Useofterminals3and4isoptional;theywillbeignoredifthe“ControlMode”is
switchedtoOFF.
• Terminals1and3are“dry”,normallyopencontacts.
• Terminals1and3areclosedwhenpoweriswithinspecications.
• Terminals1and3openwhenthereisafaultcondition.
• Terminals1and3openwhenthereisalossofthecontrolsignalwith“Control
Mode”settoON.
• Auxiliaryterminalswillbeusedinfuturemodels.
Setting the Parameters
1.PressthegreenSETUPbuttontoenterthesetupmode.SetupLEDwilllight.
2.Usethe and buttonstochangeuserparameters.
3.ScrollthroughsetupbypressingandreleasingtheSETUPbutton.
4.Whenthelastparameterhasbeenset,thephaseaveragewillbedisplayedand
thesetupLEDwillautomaticallyturnoff.
Output Voltage Condition
8VDC PhaseLoss
7VDC PhaseReversal
6VDC UnderVoltage
5VDC OverVoltage
4VDC PhaseImbalance
2VDC LoadEnergized
0VDC NoPowertoUnit
Output Conditions
Button Functions
Press to return to home screen, which alternates between line voltage
and phase average.
Press arrow to scroll through and select parameter settings in Setup
Mode.
Voltage Read Calibration:
Hold both down to calibrate line voltage. Fault and setup LEDs will flash.
Usethe
and buttonstoadjust.Press SETUP to exit calibration.
Press to enter Setup Mode and select user parameters. Setup LED
illuminates when in Setup Mode.
Press to read faults. Hold for 5 seconds to clear faults and reset memory.
Fault light will blink when fault has been added to memory.
Press and hold to reset system due to system error – this will not reset
the parameters.
To turn backlight on, press any button.
Specifications
Input
Line Voltage: 190 – 630 VAC
Frequency: 50 – 60 Hz
Load Side Monitoring: Optional
Control Voltage: 18 – 240 VAC
Control Operating Temperature
Operating Temperature: -40°F to 167°F (-40°C to 75°C)
Storage Temperature: -40°F to 185°F (-40°C to 80°C)
LCD Operating Temperature
Operating Temperature: -4°F to 167°F (-40°C to 75°C)
Mechanical
Mounting: Surface mount using two (2) #8 screws
Terminations: Screw terminals
Dimensions: 5.5”L x 4.5”W x 1.5”H
Output
Type: Relay, SPDT
Voltage Range: 240 VAC at 10A max
Frequency: 50 – 60 Hz
Remote Monitor Voltage: 0 – 10 VDC
Typical System Diagram
NO
NC
COM
CONTROL
VOLTAGE
18-240 VAC
REMOTE
MONITORING
AUX1
AUX2 AUX3 AUX4
-
+
0-10VDC
Thermostat
or Pressure
Switch
Load
Contactor
Control
Voltage
Wiring Diagram
Contactor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICM Controls ICM455 and is the answer not in the manual?

ICM Controls ICM455 Specifications

General IconGeneral
BrandICM Controls
ModelICM455
CategoryMonitor
LanguageEnglish

Related product manuals