Chapter 3 Web Configuration Page
ET-7000 AIO User Manual, Apr. 2009, V1.03, EMH-011-103----------72
Modbus Registers and Factory Defaults
Common Functions
Modbus Address Points Description Range Factory default
40557 1
Set host watch dog timer
(Second)
5~65535 (Enable)
(<5: Disable)
0 (Disable)
DO Module Functions
Modbus Address Points (Max.) Description Range Factory default
00435~00514 80 Power on value for DO 0=off / 1=on 0
00515~00594 80 Safe value for DO 0=off / 1=on 0
AI Module Functions
Modbus Address Points (Max.) Description Range Factory default
00595~00626 32 Enable/Disable AI channel
0=disabled
1=enabled
1
00628 1 Normal/Fast mode for AI
0=normal (16 bit)
1=fast (12 bit)
0
00629 1 50/60 Hz rejection for AI
0= 50 Hz
1=60 Hz
1
40296~40327 32 High alarm value for AI -32768 ~ +32767 32767
40328~40359 32 Low alarm value for AI -32768 ~ +32767 -32768
40700~40731 32 High alarm mode
0= moment
1= latched
0
40732~40763 32 Low alarm mode
0= moment
1= latched
0
40427~40458 32 Type code for AI
Refer to type code
table
Depends on
the type of
Module