Identify the incorrect splice, separate each
circuit’s neutral conductors, and re-splice
each neutral circuit’s connections.
STEP 1: ATTACH CLIPS
STEP 2: SCAN STEP 3: SEPARATE
NEUTRALS
Scan each electrical location (switch,
outlet, light fixture, etc.) with the Receiver
in the 3rd sensitivity mode setting until
you identify the highest numeric reading
on the Receiver.
The highest numerical value on the
Receiver indicates the likely location of
the incorrectly spliced conductors.
COMMON SPLICE ERROR
1. Confirm branch circuits are
de-energized
2. Use a continuity check to determine
which conductors are affected
3. Attach Transmitter alligator clips to the
affected breaker neutrals.(The two
neutrals of the AFCI/GFCI/Combo
Breakers that are nuisance tripping)
Note: The 61-948 will indicate continuity
automatically, the 61-946 requires a
separate tester.
For informational videos please go to IDEALCircuit-Tracer.com