SERVICING
50
IMAX XTRA - Installation & Servicing
69
MOTORISED DAMPER MOTOR REPLACEMENT
70
AIR DAMPER REPLACEMENT
1. Refer to Frame 49.
2. Loosen 2 securing screws from motor
cover and remove cover.
3. Disconnect electrical connections.
4. Remove 2 x M5 nuts and washers
located behind mounting plate and
remove motor.
5. Replace with new motor.
6. Re-assemble and re-wire in reverse
order.
7. Refer to Frame 49 for nal safety
checks.
2
3
1. Refer to Frame 49.
2. Remove front and inner front panels (Refer to
Frame 52).
3. If replacing Slave Module air damper rst remove
boiler LHS panel (Refer to Frame 52).
4. Remove 4 x M6 nuts, bolts and washers locating
air duct ange to venturi assembly on the module
that the air damper is to be removed.
5. Remove 2 x M5 nuts retaining air duct lower
support bracket on module that the air damper is
to be removed. Remove bracket.
6. Pull air duct assembly forward and pull air duct
anges out of automatic air duct inlet and outlet
connections.
Inspection and Replacement:
7. Check buttery aps within air damper move
freely without sticking. Remove any dust/debris
with a soft brush. Check integrity of O-ring seals
within ange connectors.
8. Re-t damper ensuring it is orientated such that
the buttery aps open inwards towards the front
of the boiler module. Also ensure inspection
window faces uppermost.
9. Re-t ductwork in reverse order to disassembly.
Check venturi ange O-ring seal is in good
condition and correctly located in its groove during
assembly.
10. Refer to Frame 49 for nal safety checks.