idealind.com
Installation Instructions - Lever & Gen II Lever
Wire Connectors
Models 52, 53, 55, L2, L3 & L5
• Do not exceed the rating of these connectors
• Turn OFF power before removing or installing connectors
• Wiring must comply with all applicable electrical regulations
• COPPER TO COPPER ONLY. Do not use on aluminium wire.
• Incorrect use of these connectors can cause electrical fires, personal injury or death
• Use only one conductor per port
• Strip wires back 9 – 10mm (52, 53 & 55) / 11-12mm (L2, L3 & L5)
• For solid and rigid stranded wire, grip wire firmly and insert conductor into open port
(lever does not need to be open)
• For flexible stranded wire (>7 strands) lift lever and insert conductor into open port. Close lever
• Verify conductors are fully inserted to the back of the connector.
• To remove a wire, lift lever and pull out wire
Specifications Model 52
2-Port Model 53 3-Port Model 55 5-Port
Rating 24 Amp / 450V /
85°C
Depth 21 mm
Width 11.9 mm 16.1 mm 24.5 mm
Height 11.7 mm
Wire Combination Range
Solid, Rigid Stranded and
Flexible Wires
0.2mm
2
-2.5mm
2
Removal
Strip Length
Insertion
2/16
Specifications Model L2
2-Port Model L3 3-Port Model L5 5-Port
Rating 32 Amp / 450V / 85
°
Depth 18.6 mm
Width 13.3 mm 18.9 mm 30.4 mm
Height 8.8 mm
Wire Combination Range
Solid and Rigid Stranded 0.2mm
2
- 4.0mm
2
Flexible Wires 0.14mm
2
- 4.0mm
2