Page #30 background imageLoading...
Page #30 background image
AUDAX TOP 6 ErP
30
10 AUDAX TOP 6 ErP TECHNICAL DATA
THE REPORTED DATA REFERS TO THE FOLLOWING CONDITIONS (in compliance with EN 14511)
:
ROOM C.H. MODE (°C) COOLING MODE (°C)
Room Antifreeze WATER (F/R)
(1)
- AIR (db/wb) 35/30 - 7/6 18/23 - 35 (db)
Room Antifreeze WATER (F/R)
(2)
- AIR (db/wb) 45/40 - 7/6 7/12 - 35 (db)
Room Antifreeze WATER (F/R)
(3)
- AIR (db/wb) 55/47 - 7/6
* Hermetically sealed system.
Central heating circuit
Power in CH mode with water set at 35 °C
(1)
kW 5.76
Power in CH mode with water set at 45 °C
(2)
kW 5.76
Power in CH mode with water set at 55 °C
(3)
kW 5.43
CH mode COP with water set at 35 °C
(1)
4.28
CH mode COP with water set at 45 °C
(2)
3.05
CH mode COP with water set at 55 °C
(3)
2.77
Min/max heat power with water set at 35 °C
(1)
kW 1.08 / 6.14
Min/max heat power with water set at 45 °C
(2)
kW 1.06 / 6.04
Min/max heat power with water set at 55 °C
(3)
kW 1.02 / 5.58
Flow temperature range °C 20 / 60
Outdoor temperature heating operation limits °C -20 / 30
Cooling circuit
Power in cooling mode with water set at 18 °C
(1)
kW 7.04
Power in cooling mode with water set at 7 °C
(2)
kW 4.73
Cooling mode EER with water set at 18 °C
(1)
3.70
Cooling mode EER with water set at 7 °C
(2)
3.00
Min/max cooling capacity with water set at 18 °C
(1)
kW 1.20 / 7.49
Min/max cooling capacity with water set at 7 °C
(2)
kW 0.73 / 5.33
Flow temperature range °C 4 / 18
Outdoor temperature Cooling operation limits °C 5 / 46
General data
Max system operating pressure bar 3
Head available on the system with 1500 l/h flow rate kPa (m H
2
O) 40 (4.08)
Expansion vessel capacity l 2
Water circuit content l 1.0
C.H. sound power level dB(A) 62
Appliance electric protection rating IP X4
Electric supply voltage V - Hz 230 - 50
Permitted voltage range V 207 - 253
Maximum absorbed power W 2000
Maximum absorbed current A 11
Fuse inserted A 16 - Type B
Refrigerant fluid load (R410A)* g 1350
Heat Pump weight kg 61
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Immergas AUDAX TOP ErP Series and is the answer not in the manual?

Immergas AUDAX TOP ErP Series Specifications

General IconGeneral
BrandImmergas
ModelAUDAX TOP ErP Series
CategoryHeat Pump
LanguageEnglish

Related product manuals