19
Display Contrast Adjustment
Press [status] and [▴] for darker display
Press [status] and [▾] for brighter display
Most FC 300 parameter set-ups can be changed
immediately via the control panel, unless a password has
been created via par. 0-60 Main Menu Password or via
par. 0-65 Quick Menu Password
Indicator lights (LEDs):
If certain threshold values are exceeded, the alarm
and/or warning LED lights up. A status and alarm text
appear on the control panel.
The ON LED is activated when the frequency converter
receives mains voltage or via a DC bus terminal or 24 V
external supply. At the same time, the back light is on. •
Green LED/On: Control section is working
Yellow LED/Warn.: Indicates a warning
Flashing Red LED/Alarm: Indicates an alarm
LCP Keys
The control keys are divided into functions. The keys
below the display and indicator lamps are used for
parameter Set-up, including choice of display indication
during normal operation. 130BP045.10
[Status] indicates the status of the frequency converter
and/or the motor. You can choose between 3 different
readouts by pressing the [Status] key:
5 line readouts, 4 line readouts or Smart Logic Control.
Use [Status] for selecting the mode of display or for
changing back to Display mode from either the Quick
Menu mode, the Main Menu mode or Alarm mode. Also
use the [Status] key to toggle single or double read-out
mode. [
Quick Menu] allows quick access to different Quick
Menus such as: -
My Personal Menu
- Quick Set-up
- Changes Made
- Loggings
Use [Quick Menu] for programming the parameters
belonging to the Quick Menu. It is possible to switch
directly between Quick Menu mode and Main Menu
mode.
[Main Menu] is used for programming all parameters. It
is possible to switch directly between Main Menu mode
and Quick Menu mode. Parameter shortcut can be
carried out by pressing down the [Main Menu] key for 3
seconds. The parameter shortcut allows direct access to
any parameter.
[Alarm Log] displays an Alarm list of the five latest
alarms (numbered A1-A5). To obtain additional details
about an alarm, use the arrow keys to maneuver to the
alarm number and press [OK]. You will now receive
information about the condition of your frequency
converter right before entering the alarm mode.
[Back] takes you to the previous step or layer in the
navigation structure.
[Cancel] annuls your last change or command as long as
the display has not been changed.
[Info] supplies information about a command, parameter,
or function in any display window. [Info] provides detailed
information whenever help is needed. Exit info mode by
pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between
the different choices available in [Quick Menu], [Main
Menu] and [Alarm Log]. Use the keys to move the
cursor.
[OK] is used for choosing a parameter marked by the
cursor and for enabling the change of a parameter.