44
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz +/- 0.003 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) ≤± 0.1 msec
System response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed control range (closed loop) 1:1000 of synchronous speed
Speed accuracy (open loop) 30 - 4000 rpm: error ±8 rpm
Speed accuracy (closed loop), depending on resolution of feedback device 0 - 6000 rpm: error ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
Control card performance:
Scan interval 1 ms
Surroundings:
Frame size B1, B2, C1 and C2 IP 21, IP 55,
Frame size D1, D2 , E1, IP 21, IP 54
Frame size E2 IP 00
Enclosure kit available ≤ 7.5 kW IP21/TYPE 1/IP 4X top
Vibration test, frame size A, B and C 1.0 g RMS
Vibration test, frame size D, E and F 0.7 g
Max. relative humidity 5% - 95%(IEC 60 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S test class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature, frame size A, B and C Max. 50 °C (24-hour average maximum 45 °C)
Ambient temperature, frame size D, E and F Max. 45 °C (24-hour average maximum 40 °C)
Derating for high ambient temperature, Contact Technical Services
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level 1000 m
Derating for high altitude, Contact Technical Services
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 550, EN 61800-3, EN 61000-6-1/2,
EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection earth. Use only an isolated laptop as PC connection