- 35 -
Quick setup
Set DI function
F4-00 DI1 function selection 1 1 (Forward run)
0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
8: IGBT enable
9: Fault reset (RESET)
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
Setting range: 0 to 59
NOTE: This signal comes from elevator controller.
F4-01 DI2 function selection 2 2 (Reverse run)
Setting range: same as DI1
NOTE: This signal comes from elevator controller.
F4-02 DI3 function selection 12 12
Setting range same as DI1
NOTE: If analog input is used as frequency reference, then DI3 is useless,
just leave it alone. If multi-reference is used as frequency reference,
then signal 'nominal speed' comes from elevator controller.
F4-03 DI4 function selection 13 13
Setting range: same as DI1
NOTE: If analog input is used as frequency reference, then DI4 is useless,
just leave it alone. If multi-reference is used as frequency reference,
then signal 'creep speed' comes from elevator controller.
F4-04 DI5 function selection 14 14
Setting range: same as DI1
NOTE: If analog input is used as frequency reference, then DI5 is useless,
just leave it alone. If multi-reference is used as frequency reference,
then signal 'inspection speed' comes from elevator controller.
F4-05 DI6 function selection 0 -
Setting range: same as DI1
CONTINUE