Inovance GA10-UPS12 - Output Specifications and Indicators

Inovance GA10-UPS12
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Item Description
Rated output voltage 24 VDC
Output voltage ripple < 80 mVp-p
Load regulation rate < ±2%
Source regulation rate < ±0.5%
Rated output current 4.0 A
Output short circuit
protection
Output is automatically cut o󶍽 upon short circuit, and output
resumes after short circuit is recti󶍾ed.
Output overvoltage
protection
When the output voltage is higher than 30 V, the AC and DC
power supplies are disabled and locked. Cut o󶍽 the power
supply and restart the product.
AC/DC e󶎀ciency
> 85% (220 VAC with full load)
> 83% (110 VAC with full load)
UPS Output
Energy storage medium Capacitor
Storage capacity
> 12 As. The holding time upon power-o󶍽 is longer than 3s for
24 V/4 A output.
Maximum backup output
time
10s
Capacitor service life > 10 years/500000 times
Charge time < 40s
Rated output current 4.0 A
State Output
Signal interface Opto-coupler isolation
Signal speci󶍾cation 5-24 VDC, 30 mA
State output
signal
Input
detection (AC
OK)
When the AC input is powered on, the dry contact is
energized.
When the AC input is powered o󶍽, the dry contact is
disconnected.
Startup
signal
When the AC input is powered on, a 500 ms pulse is energized
and input to simulate the power-on signal. When the power
supply is turned on and o󶍽 quickly (the power-o󶍽 time is less
than 10s), the controller cannot detect the power-on state;
therefore, the product cannot be turned on. In this case,
the simulated power-on signal can be used to turn on the
product.
Indicators
AC OK
Input
detection
Green, steady on: The input power supply is normal.
Green, steady o󶍽: The input power supply fails.