253
4
4 Instructions 4.6.4 Matrix Rotation and Shift
When the number of characters contained in the new string is even, 0000H is stored in the element after the one
that stores the last character.
When the value in [S1] or [S2] starts from 00H (which indicates the number of characters is 0), 0000H is stored in
[D].
An error is returned in the following conditions. The error ag M8067 is set to ON to identify this error and
the error code is stored in D8067.
Error 6705 is returned when 00H is not found in the operand ranges of [S1] and [S2].
Error 6705 is returned when the string after combination exceeds the operand range of [D].
Error 6706 is returned when [S1] and [S2] have overlapping elements with [D].