625
9
9 Communication 9.6.3 CANlink Software Conguration
3) The following window is displayed.
a) Net Info
Baud Rate
: Indicates the baud rate of the master station.
Net Heartbeat
: The heartbeat function is enabled by selecting this parameter.
Net Load
: Computes the real-time load of the network (this parameter is displayed only when the network
load is monitored during running of devices).
Network load ≤ 50: Green (good)
50 < Network load ≤ 75: Yellow (warning)
75 < Network load ≤ 90: Red (major warning)
Network load > 90: ERR, red background (error)
Site status monitor
After
Enable monitor
is selected, the online state of the slave station will be updated to the corresponding
D soft element (head address of the monitored register + station number). The default head address is
D7800. For example, if station 2 is to be monitored, the state will be displayed in D7802.
Register Status Denition
1 Congurations of the slave station are available.
2 The slave station is running.
5 The slave station is disconnected.
If the heartbeat function is not enabled, station state monitoring is disabled.