EasyManua.ls Logo

Inovance H3U Series - Page 664

Inovance H3U Series
737 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
663
10
10 Extension Modules
10.2.2 Digital Input Module (AM600-1600END)
SN
Network
Name
Type Function Remarks
The 2nd Group of Input Interfaces
9 I0 Input
The 2nd group of user
input 0
SINK/SOURCE input
10 I1 Input
The 2nd group of user
input 1
SINK/SOURCE input
11 I2 Input
The 2nd group of user
input 2
SINK/SOURCE input
12 I3 Input
The 2nd group of user
input 3
SINK/SOURCE input
13 I4 Input
The 2nd group of user
input 4
SINK/SOURCE input
14 I5 Input
The 2nd group of user
input 5
SINK/SOURCE input
15 I6 Input
The 2nd group of user
input 6
SINK/SOURCE input
16 I7 Input
The 2nd group of user
input 7
SINK/SOURCE input
Common
17 SS Power Common -
18 SS Power Common -
External wiring
Digital input module wiring diagram
DC 24 V
SS
DC 24 V
OPtocoupler
insulation
OPtocoupler
insulation
~~
0I
7I

0I

7I
~~
SINK signal
input mode
OPtocoupler
insulation
OPtocoupler
insulation
SOURCE signal
input mode
Internal
circuit
(3) Module usage
When a local digital input extension module is connected to the main module, the SN of the X port on
the extension module follows that of the X port on the main module. For example, the main module H3U
connects the AM600-1600END. The SN of the last X port of the main module is X37. The SNs of the 16 X
ports of the extension module are X40 to X47 and X50 to X57. Use the same method to number X ports of
the following digital input extension modules.

Table of Contents

Other manuals for Inovance H3U Series

Related product manuals