673
10
10 Extension Modules
10.2.4 Analog Input Module (AM600-4AD)
The relationship between mapping and actual input analog value is as follows:
Rated Input
Range
Rated Digital
Value
Input Limit Range
Limiting Digital
Value
Analog
voltage input
–10 V to +10 V
–20,000 to
+20,000
–11 V to +11 V –22,000 to +22,000
0 V to 10 V 0 to 20,000 –0.5 V to +10.5 V –1000 to +21,000
–5 V to +5 V
–20,000 to
+20,000
–5.5 V to +5.5 V –22,000 to +22,000
0 V to 5 V 0 to 20,000
–0.25 V to +5.25
V
–1000 to +21,000
1 V to 5 V 0 to 20,000 0.8 V to 5.2 V –1000 to +21,000
Analog
current input
–20 mA to +20
mA
–20,000 to
+20,000
–22 mA to +22
mA
–22,000 to +22,000
0 mA to 20 mA 0 to 20,000 –1 mA to +21 mA –1000 to +21,000
4 mA to 20 mA 0 to 20,000
3.2 mA to 20.8
mA
–1000 to +21,000
④ Use ladder graphic programming language to program AD sampling. Change mapping tag of CH0 from
D200 to D0.
Network 1
The sampling value of voltage channel 0 of AM600-4AD is assigned to D0.
Program running status
Network 2 Network comment
Network 3 Network comment
⑤ After successful compiling, download the project and run it.
The program is running.