10.2.5 Analog Output Module (AM600-4DA)
SN
Network
Name
Type Function Remarks
9 V+ Output V+ of channel 2 Voltage output
10 VI- Output V-/I- of channel 2
Voltage/Current
output
11 I+ Output I+ of channel 2 Current output
12 - Shielding ground
Internally
connected to
housing ground
13 V+ Output V+ of channel 3 Voltage output
14 VI- Output V-/I- of channel 3
Voltage/Current
output
15 I+ Output I+ of channel 3 Current output
16 AGND
Analog
ground
Analog ground -
17 24 V Power 24 V power supply -
18 COM
Power
ground
Power ground -
●
External wiring
① Connection for voltage-controlled signal
• Use 2-core shielded twisted pair cable as power cable.
• If noises or ripples are generated in external wiring, connect a capacitor of 0.1 to 0.47mF, 25V between terminals
V+/I+ and VI-.