10 Extension Modules
10.2.5 Analog Output Module (AM600-4DA)
Digital
conversion
*1
*2
+15V
-15V
+24V
DC/DC
converter
Fliter
24Vdc
external power
24V
COM
I+
VI-
Motor drive
module, etc
100Ω
to
600Ω
FG
AGND
AGND
V+
(b) Current output
② Connection for current-controlled signal
• Use 2-core shielded twisted pair cable as power cable.
• If noises or ripples are generated in external wiring, connect a capacitor of 0.1 to 0.47mF25V between terminals
V+/I+ and VI-.
③ Wiring precautions
Do not bundle the cable together with AC cable, main lines, high voltage cable and so forth; otherwise, it
may result in an increased noise, surge and induction.
Apply single-point grounding for the shielding of shielded cable and solder sealed cable.
Tubed and solderless crimp terminal cannot be used with terminal block. Using marking sleeve or insulation
sleeve to cover the cable connector part of the crimp terminals is recommended.
3) Example for H3U+AM600-4DA Programming
① Select the module AM600-4DA to be added from the module list. Double-click the module to
automatically add it to the extension rack, or use the left mouse button to drag it onto the extension
rack.
② Double-click the AM600-4DA module on the rack, and the conguration interface appears (as below).