677
10
10 Extension Modules
10.2.5 Analog Output Module (AM600-4DA)
On the
General Conguration
interface of the AM600-4DA module, enable Channel-0, and congure
Conversion Mode
as
-10V~10V
voltage output.
State Output After Stop
can also be congured.
On the conguration interface, enable the corresponding channel. Disable unused channels to reduce the
scan duration.
Select voltage or current of different modes from the
Translate Mode
drop-down list. In this example,
Translate Mode
is congured as
-10V~10V
voltage output.
Output state after Stopping
sets the module output condition when the PLC is in the stopped state. The
options include
Output zero
,
Output hold
, and
Output preset
.