678
10
10 Extension Modules
10.2.5 Analog Output Module (AM600-4DA)
③ On the
IO Map
tab page, map CH0 of 4DA module to D0 of element D.
The relationship between elements and actual analog values is as follows:
Rated Output
Range
Rated Digital Value Output Limit Range Limiting Digital
Value
Analog Voltage
Output
–10 V to +10 V –20,000 to +20,000 –11 V to +11 V –22,000 to +22,000
0 V to 10 V 0 to 20,000 –0.5 V to +10.5 V –1000 to +21,000
–5 V to +5 V –20,000 to +20,000 –5.5 V to +5.5 V –22,000 to +22,000
0 V to 5 V 0 to 20,000 –0.25 V to +5.25 V –1000 to +21,000
1 V to 5 V 0 to 20,000 0.8 V to 5.2 V –1000 to +21,000
Analog current
output
0 mA to 20 mA 0 to 20,000 0 mA to 21 mA 0 to 21,000
4 mA to 20 mA 0 to 20,000 3.2 mA to 20.8 mA –1000 to +21,000