EasyManua.ls Logo

Inovance H3U Series - Page 679

Inovance H3U Series
737 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
678
10
10 Extension Modules
10.2.5 Analog Output Module (AM600-4DA)
On the
IO Map
tab page, map CH0 of 4DA module to D0 of element D.
The relationship between elements and actual analog values is as follows:
Rated Output
Range
Rated Digital Value Output Limit Range Limiting Digital
Value
Analog Voltage
Output
–10 V to +10 V –20,000 to +20,000 –11 V to +11 V –22,000 to +22,000
0 V to 10 V 0 to 20,000 –0.5 V to +10.5 V –1000 to +21,000
–5 V to +5 V –20,000 to +20,000 –5.5 V to +5.5 V –22,000 to +22,000
0 V to 5 V 0 to 20,000 –0.25 V to +5.25 V –1000 to +21,000
1 V to 5 V 0 to 20,000 0.8 V to 5.2 V –1000 to +21,000
Analog current
output
0 mA to 20 mA 0 to 20,000 0 mA to 21 mA 0 to 21,000
4 mA to 20 mA 0 to 20,000 3.2 mA to 20.8 mA –1000 to +21,000