4 Quick Setup
- 23 -
START Para. Parameter Name Default Commission
Set motor parameters
.
Motor Nameplate
F1-01 Rated motor power model dependent 1.5
Unit: kW
F1-02 Rated motor voltage model dependent 380
Unit: V
F1-03 Rated motor current model dependent 3.4
Unit: A
F1-04 Rated motor frequency model dependent 50
Unit: Hz
F1-05 Rated motor speed model dependent 2800
Unit: rpm.
Perform motor auto-tuning
.
F1-37 Auto-tuning selection 0 1
0: No auto-tuning
1: Static auto-tuning
Auto-tuning procedure:
1. Ensure the UVW connection between AC drive and motor is not cut off by output
contactor; if it is cut off, then manually handle with the output contactor.
2. Set F0-02 = 0 (operating panel), so that the key
can start the tuning procedure.
3. Set F1-37 = 1, press
, then LED on the panel will display letters "TUNE".
4. Press the key
on the panel, then motor starts auto-tuning, it usually takes about
30 seconds to nish this auto-tuning, wait until LED stops displaying "TUNE"
Select a command source. F0-02 Command source selection 1
0: Operating panel (keypad & display)
1: Terminal I/O control
2: Serial comms.
Select a frequency reference
setting channel
.
F0-03
Main frequency reference setting channel
selection
0
0: Digital setting F0-08 (pressing or to change the value of F0-08 easily, and
the changed value will not be cleared even after power off)
1: Digital setting F0-08 (pressing or to change the value of F0-08 easily, but the
changed value will be cleared after power off)
2: AI
5: Pulse setting (DI4)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting
CONTINUE Para. Parameter Name Default Commission