4 Quick Setup
- 24 -
CONTINUE Para. Parameter Name Default Commission
If F0-08 is frequency reference
Set F0-08 F0-08 Preset frequency 50.00
If AI is frequency reference
0 Hz to F0-10
Set AI F4-13 AI curve minimum input 0.00
If multi-reference is frequency
reference
0 V to F4-15;
F4-14 Corresponding percentage of AI minimum
input
0.0
-100.0% to 100.0%
F4-15 AI maximum input 10.00
F4-13 to 10.00 V
F4-16 Corresponding percentage of AI maximum
input
100.0
-100.0% to 100.0%
Set multi-reference values
.
FC-00
Reference 0
0.0
If any digital input is used
0.0% to 100.0%
FC-01 to
FC-07
Reference 1o reference 7
0.0
0.0% to 100.0%
Set DI function F4-00 DI1 function selection 1
0: No function
1: Forward run (FWD)
2: Reverse run (REV)
3: Three-wire control
4: Forward jog (FJOG)
5: Reverse jog (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN disabled
11: External fault normally-open input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
16: Terminal 1 for acceleration/deceleration time selection
18: Frequency reference setting channel switchover
19: UP and DOWN setting clear (terminal, operating panel)
20: Command source switchover
21: Acceleration/Deceleration prohibited
22: PID disabled
23: PLC state reset
CONTINUE Para. Parameter Name Default Commission
CONTINUE Para. Parameter Name Default Commission