4 Quick Setup
- 26 -
Set the DO function
.
F5-02 Relay function selection(T/A-T/C) 2
If an analog output is used
31: AI input exceeding limit
32: Load lost
33: Reverse running
34: Zero current
36: Output current exceeding limit
37: Frequency lower limit reached (having output at stop)
38: Alarm output
40: Current running time reached
41: Fault output
Set the AO function
.
F5-07 AO function selection 0
0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: Pulse input (100% corresponding to 20 kHz)
7: AI
12: Communication setting
13: Motor rotational speed
14: Output current (100% corresponding to 100 A)
15: Output voltage (100% corresponding to 1000 V)
Set accel. /decel. time
.
F0-17 Acceleration time 1 Model dependent
If smooth accel./decel. is
requested
0.0 to 6500.0s
F0-18 Deceleration time 1 Model dependent
0.0 to 6500.0s
Set S-curve
.
F6-07 Acceleration/Deceleration mode 0
0: Linear acceleration/deceleration
1: Static S-curve acceleration/deceleration
2: Dynamic S-curve acceleration/deceleration
F6-08 Time proportion of S-curve at Accel. start 30.0
0.0% to (100.0% - F6-09)
F6-09 Time proportion of S-curve at Accel. end 30.0
0.0% to (100.0% - F6-08)
CONTINUE Para. Parameter Name Default Commission