5 Parameter Table
- 29 -
Para. No. Para. Name Setting Range Default Comms. Address
F0-18 Deceleration time1
0.00 to 650.00s (F0-19=2)
0.0 to 6500.0s (F0-19=1)
0 to 65000s (F0-19=0)
Model
dependent
0xF012/0x0012
F0-19
Acceleration/deceleration time
unit
0: 1s
1: 0.1s
2: 0.01s
1 0xF012/0x0013
F0-23
Retentive of digital setting
frequency upon stop
0: Not retentive
1: Retentive
0 0xF017/0x0017
F0-25
Acceleration/Deceleration time
base frequency
0: Maximum frequency (F0-10)
1: Frequency reference
2: 100 Hz
0 0xF019/0x0019
F0-26
Base frequency for UP/DOWN
modication during running
0: Running frequency
1: Frequency Reference
0 0xF01A/0x001A
Group F1: Motor 1 Parameters
F1-01 Rated motor power 0.1 to 5.5 kW
Model
dependent
0xF101/0x0101
F1-02 Rated motor voltage 1 to 600 V
Model
dependent
0xF102/0x0102
F1-03 Rated motor current 0.01 to 30.00 A
Model
dependent
0xF103/0x0103
F1-04 Rated motor frequency 0.01 Hz to max. frequency
Model
dependent
0xF104/0x0104
F1-05 Rated motor speed 1 to 65535 rpm
Model
dependent
0xF105/0x0105
F1-06
Asynchronous motor stator
resistance
0.001 to 65.535 ohm
Auto-tuning
dependent
0xF106/0x0106
F1-07
Asynchronous motor rotor
resistance
0.001 to 65.535 ohm
Auto-tuning
dependent
0xF107/0x0107
F1-08
Asynchronous motor leakage
inductive reactance
0.001 to 65.535 mH
Auto-tuning
dependent
0xF108/0x0108
F1-09
Asynchronous motor mutual
inductive reactance
0.001 to 65.535 mH
Auto-tuning
dependent
0xF109/0x0109
F1-10
Asynchronous motor no-load
current
0.01A to F0-03
Auto-tuning
dependent
0xF109/0x010A
F1-37
Motor auto-tuning method
selection
0: No auto-tuning
1: Static auto-tuning 1
2: Complete auto-tuning
0 0xF125/0x0125
Group F2: Vector Control Parameters
F2-00 Speed loop proportional gain 1 1 to 100 30 0xF200/0x0200
F2-01 Speed loop integral time 1 0.01 to 10.00s 0.50s 0xF201/0x0201
F2-02 Switchover frequency 1 0.00 to F2-05 5.00 Hz 0xF202/0x0202
F2-03 Speed loop proportional gain 2 1 to 100 20 0xF203/0x0203
F2-04 Speed loop integral time 2 0.01 to 10.00s 1.00s 0xF204/0x0204
F2-05 Switchover frequency 2 F2-02 to maximum frequency 10.00 Hz 0xF205/0x0205
F2-06 SVC/FVC slip compensation gain 50% to 200% 100% 0xF206/0x0206
F2-07 SVC speed feedback lter time 0.000 to 0.100s 0.050s 0xF207/0x0207
F2-08
Vector control over-excitation
gain
0 to 200 0 0xF208/0x0208