Function Code Table
MD280 User Manual
- 92 -
Function
Code
Parameter Name Setting Range
Min.
Unit
Default
Property
FB-05
Overcurrent stall
gain
0–100 1 20
ƿ
FB-06
Overcurrent stall
protective current
100%–200% 1% 150%
ƿ
FB-07
Short-circuit to
ground upon
power-on
0: Disabled
1: Enabled
11
ƿ
FB-08
Protection upon off-
load
0: Disabled
1: Enabled
10
ƿ
FB-09
Power dip ride-
through function
0: Disabled
1: Enabled
10
ƿ
FB-10
Power dip ride-
through frequency
decline rate
+]VWRPD[LPXP
IUHTXHQF\)V
0.01 Hz/
s
10.00 Hz/s
ƿ
FB-11
Voltage rise judging
time of power dip
ride-through
0.00–100.00s 0.01s 0.50s
ƿ
FB-12
Judging voltage
of power dip ride-
through action
60.0%–100.0% 1% 80.0%
ƿ
FB-13
Fault auto reset
times
0–10 1 0
ƿ
FB-14
DO action during
fault auto reset
0: No
1: Yes
10
ƿ
FB-15
Time interval of
fault auto reset
0.1–60.0s 0.1s 1.0s
ƿ
FB-16
Clear time of fault
auto reset times
0.1–1000.0 h 0.1 h 1.0 h
ƿ
FB-17
Input phase loss
protectio
0: Disabled
1: Enabled
11
ƿ
FB-18
Output phase loss
protection
0: Disabled
1: Enabled
11
ƿ
FB-19
Heatsink
temperature of
inverter module
-10 to 100.0°C 1°C -
ƽ
FB-20 1st fault type
0: No fault
1: Reserved
2: Overcurrent during
DFFHOHUDWLRQ(55
3: Overcurrent during
GHFHOHUDWLRQ(55
7REHFRQWLQXHG
--
ƽ