48
Setting range 0 Hz ~ maximum frequency
When the frequency source is selected as F0-02=5, the values of F6-14 to F6-17 must be set.
F6-18 Heatsink temperature
Default
Displaying range Displaying the actual temperature of the heatsink
F6-19 Software version No.
Displaying the software version.
F7 Group: Communication Parameter
This parameter must be set when the inverter needs to be controlled by the upstream device
through serial communication ports.
F7-00 Baud rate
Default 5
0 300BPS
1 600BPS
2 1200BPS
3 2400BPS
4 4800BPS
5 9600BPS
6 19200BPS
Setting
range
7 38400BPS
This parameter is used for determining the rate of the serial communication.
F7-01 Data format
Default 0
0 No parity
1 Even parity
Setting
range
2 Odd parity
The data formats set by the upstream device and inverter must be consistent, otherwise it cannot
communicate.
F7-02 Local address Default 1
Setting range 0 ~ 247, 0: broadcasting address
When the local address is set to 0, i.e. broadcasting address, it enables the broadcasting function of
the upstream device.
The local address is unique (except for the broadcasting address), which is the basis of realizing
point to point communication between the upstream device and the inverter.
F7-03 Response time delay
Default 2ms
Setting range 0ms~20ms