MD380 User Manual Function Code Table
- 105 -
Function
Code
Parameter Name
Setting Range
Default Property
F9-49
Fault protection action
selection 3
Unit's digit (User-dened fault 1,
Err27)
00000
Same as unit's digit in F9-47
Ten's digit (User-dened fault 2,
Err28)
Same as unit's digit in F9-47
Hundred's digit (Accumulative
power-on time reached, Err29)
Same as unit's digit in F9-47
Thousand's digit (Load becoming
0, Err30)
0: Coast to stop
1: Stop according to the stop
mode
2: Continue to run at 7% of rated
motor frequency and resume
to the set frequency if the load
recovers
Ten thousand's digit (PID
feedback lost during running,
Err31)
Same as unit's digit in F9-47
F9-50
Fault protection action
selection 4
Unit's digit (Too large speed
deviation, Err42)
00000
Same as unit's digit in F9-47
Ten's digit (Motor over-speed,
Err43)
Same as unit's digit in F9-47
Hundred's digit (Initial position
fault, Err51)
Same as unit's digit in F9-47
Thousand's digit (Speed feedback
fault, Err52)
Same as unit's digit in F9-47
Ten thousand's digit: Reserved
F9-54
Frequency selection for
continuing to run upon fault
0: Current running frequency
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
0