MD380 User Manual Desc
ription of Function Codes
- 187 -
)unction Code Parameter Name Setting Range Default
)7-09 Accumulative running time 0–65535 h -
It is used to display the accumulative running time of the AC drive. After the accumulative
UXQQLQJWLPHUHDFKHVWKHYDOXHVHWLQ)WKHWHUPLQDOZLWKWKHGLJLWDORXWSXWIXQFWLRQ
becomes ON.
)unction Code Parameter Name Setting Range Default
)7-10 Product number AC drive product number -
)7-11 Software version Software version of control board -
)7-12
Number of decimal
places for load speed
display
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
1
)LVXVHGWRVHWWKHQXPEHURIGHFLPDOSODFHVIRUORDGVSHHGGLVSOD\7KHIROORZLQJ
gives an example to explain how to calculate the load speed:
$VVXPHWKDW)/RDGVSHHGGLVSOD\FRHIILFLHQWLV DQG ) LV GHFLPDO
places). When the running frequency of the AC drive is 40.00 Hz, the load speed is 40.00 x
2.000 = 80.00 (display of 2 decimal places).
If the AC drive is in the stop state, the load speed is the speed corresponding to the set
frequency, namely, "set load speed". If the set frequency is 50.00 Hz, the load speed in the
stop state is 50.00 x 2.000 = 100.00 (display of 2 decimal places).
)unction Code Parameter Name Setting Range Default
)7-13 Accumulative power-on time 0–65535 h 0 h
It is used to display the accumulative power-on time of the AC drive since the delivery. If the
WLPHUHDFKHVWKHVHWSRZHURQWLPH)WKHWHUPLQDOZLWKWKHGLJLWDORXWSXWIXQFWLRQ
becomes ON.
)unction Code Parameter Name Setting Range Default
)7-14 Accumulative power consumption 0–65535 kWh /
It is used to display the accumulative power consumption of the AC drive until now.
Group )8: Auxiliary )unctions
)unction Code Parameter Name Setting Range Default
)8-00 JOG running frequency 0.00 Hz to maximum frequency 2.00 Hz
)8-01 JOG acceleration time 0.0–6500.0s 20.0s
)8-02 JOG deceleration time 0.0–6500.0s 20.0s
7KHVHSDUDPHWHUVDUHXVHGWRGH¿QHWKHVHWIUHTXHQF\DQGDFFHOHUDWLRQGHFHOHUDWLRQWLPH
RIWKH$&GULYHZKHQMRJJLQJ7KHVWDUWXSPRGHLV'LUHFWVWDUW)DQGWKHVWRS
PRGHLV'HFHOHUDWHWRVWRS) GXULQJMRJJLQJ