)ault Name Display Possible Causes Solutions
Overcurrent at
constant speed
Err04
1: T
he output circuit is grounded
or short circuited.
2: Motor auto-tuning is not
performed.
3: The voltage is too low.
4: A
sudden load is added during
operation.
5: The AC drive model is of too
small power class.
1: Eliminate external faults.
2: Perform the motor auto-
tuning.
3: A
djust the voltage to
normal range.
4: Remove the added load.
5: Select an A
C drive of
higher power class.
Overvoltage
during
acceleration
Err05
1: T
he input voltage is too high.
2: An external force drives the
motor during acceleration.
3: T
he acceleration time is too
short.
4: The braking unit and braking
resistor are not installed.
1: A
djust the voltage to
normal range.
2: Cancel the external force
or install a braking resistor.
3: Increase the acceleration
time.
4: Install the braking unit and
braking resistor.
Overvoltage
during
deceleration
Err06
1: T
he input voltage is too high.
2: An external force drives the
motor during deceleration.
3: The deceleration time is too
short.
4: T
he braking unit and braking
resistor are not installed.
1: A
djust the voltage to
normal range.
2: Cancel the external force
or install the braking resistor.
3: Increase the deceleration
time.
4: Install the braking unit and
braking resistor.
Overvoltage at
constant speed
Err07
1: T
he input voltage is too high.
2: A
n external force drives the
motor during deceleration.
1: A
djust the voltage to
normal range.
2: Cancel the external force
or install the braking resistor.
Control power
supply fault
Err08
The input voltage is not within the
allowable range.
Adjust the input voltage to
the allowable range.
Undervoltage Err09
1: Instantaneous power failure
occurs on the input power supply.
2: T
he AC drive's input voltage is
not within the allowable range.
3: The bus voltage is abnormal.
4: The recti¿er bridge and buffer
resistor are faulty.
5: T
he drive board is faulty.
6: The main control board is faulty.
1: Reset the fault.
2: Adjust the voltage to
normal range.
3: Contact the agent or
Inovance.
AC drive overload Err10
1: T
he load is too heavy or locked-
rotor occurs on the motor.
2: The AC drive model is of too
small power class.
1: Reduce the load and
check the motor and
mechanical condition.
2: Select an AC drive of
higher power class.