MD380 User Manual Function Code Table
- 83 -
)unction
Code
Parameter Name
Setting Range
Default Property
)0-27
%inding command source to
frequency source
8QLWVGLJLW%LQGLQJRSHUDWLRQ
panel command to frequency
source)
000 ƿ
0: No binding
)UHTXHQF\VRXUFHE\GLJLWDO
setting
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
7HQVGLJLW%LQGLQJWHUPLQDO
command to frequency source)
0–9, same as unit's digit
+XQGUHGVGLJLW%LQGLQJ
communication command to
frequency source)
0–9, same as unit's digit
)0-28
Serial communication
protocol
0: Modbus protocol
3UR¿EXV'3EULGJH
2: CANopen bridge
0 ƿ
Group )1: Motor 1 Parameters
)1-00 Motor type selection
0: Common asynchronous motor
1: Variable frequency
asynchronous motor
2: Permanent magnetic
synchronous motor
1 ƾ
)1-01 Rated motor power
0.1–1000.0 kW
Model
dependent
ƾ
)1-02 Rated motor voltage
1–2000 V
Model
dependent
ƾ
)1-03 Rated motor current
±$$&GULYHSRZHU
55 kW)
±$$&GULYHSRZHU!
55 kW)
Model
dependent
ƾ
)1-04 Rated motor frequency
0.01 Hz to maximum frequency
Model
dependent
ƾ
)1-05
Rated motor rotational
speed
1–65535 RPM
Model
dependent
ƾ
efesotomasyon.com