Communication Parameters
‑25‑
Parameter Address Parameter Description
Input of control commands to the AC
drive 1 (write‑only)
7311H 0: Stop mode set by F6‑10 (Stop mode)
1: Forward run
2: Reverse run
3: Forward jog
4: Reverse jog
5. Coast to stop
6: Stop mode set by F6‑10 (Stop mode)
7: Fault reset
Input of control commands to the AC
drive 2 (write‑only)
2000H 1: Forward run
2: Reverse run
3: Forward jog
4: Reverse jog
5. Coast to stop
6: Decelerate to stop
7: Fault reset
Read AC drive status 1 3000H 1: Forward run
2: Reverse run
3: Stop
4: Auto‑tuning
5: Fault
Read AC drive status 2 7044H Bit0: Running status
Bit1: Forward/Reverse state
Bit2: Whether fault occurs
Bit3: Whether output frequency
reaches the frequency reference
Bit4: Communication normal flag
Bit5–7: Reserved
Bit8–15: Fault code
Parameter locking password check 1F00H Parameter locking password check: If
an actual password value is returned, it
indicates that password check passes.
If no password is set, namely, the
password is 0, 0000H is returned.
Initialize parameters. 1F01H 1: Restore factory settings
4: Restore user backup parameters
501: Back up the current user
parameters
DO control 2001H BIT0: DO1 control
BIT1: DO2 control
BIT2: RELAY1 output control
BIT3: RELAY2 output control
BIT4: FMR output control
BIT5: VDO1
BIT6: VDO2
BIT7: VDO3
BIT8: VDO4
BIT9: VDO5
AO1 control (write‑only) 2002H 0 to 7FFF indicate 0% to 100%