Electrical Installation
‑123‑
The copper busbars in the preceding figures can be removed as required. The
following figure shows the dimensions of the main circuit terminals without copper
busbars.
300
35
161.5
60
35
135
62
33
33
14-M12
S
R
T
U
V
W
Figure 7‑19 Main circuit terminal dimensions of T10 models (without copper busbars and
output reactors)
Table 7–12 Recommended main circuit cables for T10 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T10
MD500T200G‑PLUS
MD500T200G‑L‑PLUS
365.0
2 x (3 x 95)
BC95‑12 95 BC95‑12 M12
35.0 (310.1)
MD500T220G‑PLUS
MD500T220G‑L‑PLUS
410.0
2 x (3 x 120)
BC120‑12 120 BC120‑12 M12
35.0 (310.1)
T11
U
V
W
60
36
330
62
65
139
29
65.2
62
42
29
146
29
29
8-M12
133
33
115115193.5
50
192.5 85
50
2 13
Figure 7‑20 Main circuit terminal dimensions of T11 models (without output reactors)