Electrical Installation
‑125‑
Table 7–13 Recommended main circuit cables for T11 models
Struc‑
ture
Model
Rated
Input
Current
A
RST/UVW
Grounding Wire
Screw
Tightening
Torque
N•m (lbf•in.)
Cable
(mm
2
)
<1>
Cable Lug
Cable
(mm
2
)
<1>
Cable Lug
T11
MD500T250G‑PLUS
MD500T250G‑L‑PLUS
441.0
2 x (3 x 120)
BC120‑12 120 BC120‑12 M12
35.0 (310.1)
MD500T280G‑PLUS
MD500T280G‑L‑PLUS
495.0
2 x (3 x 150)
BC150‑12 150 BC150‑12 M12
35.0 (310.1)