Parameter List
38
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F8‑48 0xF830 Cooling fan
working mode
0: Working during drive
running
1: Working continuously
0 In real time "
F8‑48
"
on
page 238
F8‑49 0xF831 Wakeup frequency F8‑51 to F0‑10 0 Hz In real time "
F8‑49
"
on
page 238
F8‑50 0xF832 Wakeup delay 0.0s to 6500.0s 0 s In real time "
F8‑50
"
on
page 238
F8‑51 0xF833 Hibernation
frequency
0.00 Hz to F8‑49 0 Hz In real time "
F8‑51
"
on
page 238
F8‑52 0xF834 Hibernation delay 0.0s to 6500.0s 0 s In real time "
F8‑52
"
on
page 239
F8‑53 0xF835 Current running
time threshold
0.0 min to 6500.0 min 0 min In real time "
F8‑53
"
on
page 239
F8‑55 0xF837 Emergency stop
deceleration time
0.0s to 6500.0s 0 s In real time "
F8‑55
"
on
page 239
F8‑57 0xF839 Accumulative
power
consumption
cleared
0: Disabled
1: Enabled
0 At stop "
F8‑57
"
on
page 240
F8‑58 0xF83A Output power
correction
coefficient
0.0% to 200.0% 100 % At stop "
F8‑58
"
on
page 240
F9‑00 0xF900 AC drive overload
protection
0: Disabled
1: Enabled
0 In real time "
F9‑00
"
on
page 240
F9‑01 0xF901 Motor overload
protection gain
0.2 to 10.00 1 In real time "
F9‑01
"
on
page 241
F9‑02 0xF902 Motor overload
pre‑warning
coefficient
50% to 100% 80 % In real time "
F9‑02
"
on
page 241
F9‑04 0xF904 Overvoltage
threshold
350.0820.0 V 820 V In real time "
F9‑04
"
on
page 242
F9‑06 0xF906 Output phase loss
detection before
startup
0: Invalid
1: Valid
0 In real time "
F9‑06
"
on
page 242
F9‑07 0xF907 Detection of short
circuit to ground
0: No detection
1: Detection before power‑on
2: Detection before running
3: Detection before power‑on
and running
1 At stop "
F9‑07
"
on
page 242
F9‑08 0xF908 Braking unit action
start voltage
200.0 V to 2000.0 V 760 V In real time "
F9‑08
"
on
page 242
F9‑09 0xF909 Fault auto reset
times
0 to 20 0 In real time "
F9‑09
"
on
page 243
F9‑10 0xF90A DO action during
auto fault reset
0: Disabled
1: Enabled
0 In real time "
F9‑10
"
on
page 243