Parameter List
‑68‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
A9‑13 0xA90D Quick auto‑tuning
of stator
resistance
coefficient 1 of
asynchronous
motor
0 to 65535 10 ‑ At stop "
A9‑13
"
on
page 368
A9‑14 0xA90E Quick auto‑tuning
of stator
resistance
coefficient 2 of
asynchronous
motor
0 to 65535 10 ‑ At stop "
A9‑14
"
on
page 368
A9‑17 0xA911 Synchronous
motor real‑time
angle
0.0 to 359.9 0 ‑ Unchangea
ble
"
A9‑17
"
on
page 368
A9‑18 0xA912 Initial position
angle detection of
synchronous
motor
0: Detected upon running
1: Not detected
2: Detected upon initial
power‑on
0 ‑ In real time "
A9‑18
"
on
page 369
A9‑20 0xA914 Flux weakening
mode selection
0: Automatic mode
1: Synchronous motor
adjustment mode
2: Synchronous motor hybrid
mode
3: Disabled
1 ‑ At stop "
A9‑20
"
on
page 369
A9‑21 0xA915 Flux weakening
gain of
synchronous
motor
0 to 50 5 ‑ In real time "
A9‑21
"
on
page 369
A9‑22 0xA916 Output voltage
upper limit margin
of synchronous
motor
0% to 50% 5 % In real time "
A9‑22
"
on
page 369
A9‑23 0xA917 Maximum force
adjustment gain of
synchronous
motor
20% to 300% 100 % In real time "
A9‑23
"
on
page 370
A9‑24 0xA918 Exciting current
adjustment gain
calculated by
synchronous
motor
40% to 200% 100 % In real time "
A9‑24
"
on
page 370
A9‑25 0xA919 Estimated
synchronous
motor speed
integral gain in
SVC mode
5% to 1000% 30 % In real time "
A9‑25
"
on
page 370