Parameter List
‑71‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
A9‑51 0xA933 Advanced settings
for asynchronous
motor parameter
auto‑tuning
Ones: Rotor resistance and
leakage inductance DC offset
0: Standard offset
1: Large offset
Tens: New rotor resistance
and leakage inductance auto‑
tuning algorithm
0: Disabled
1: Enabled
111 At stop "
A9‑51
"
on
page 376
Contin
ued
Contin
ued
Continued Hundreds: New mutual
inductance static auto‑tuning
algorithm
0: Disabled
1: Enabled
Thousands: Stator resistance
auto‑tuning algorithm
0: Current open loop
1: Current closed loop
Contin
ued
Contin
ued
Continued Continued
A9‑52 0xA934 U0‑06 feedback
torque selection
0: Motoring torque being
positive and generating
torque being negative
1: Torque direction being
positive in the case of positive
speed direction; torque
direction being negative in the
case of negative speed
direction
1 In real time "
A9‑52
"
on
page 377
A9‑54 0xA936 Transistor voltage
drop
0 to 10000 700 At stop "
A9‑54
"
on
page 377
A9‑55 0xA937 Dead‑zone time 0 0 to 10000 352 At stop "
A9‑55
"
on
page 377
A9‑56 0xA938 Dead‑zone time 1 0 to 10000 1052 At stop "
A9‑56
"
on
page 377
A9‑57 0xA939 Dead‑zone time 2 0 to 10000 1270 At stop "
A9‑57
"
on
page 378
A9‑58 0xA93A Dead‑zone time 3 0 to 10000 1358 At stop "
A9‑58
"
on
page 378
A9‑59 0xA93B Dead‑zone time 4 0 to 10000 1404 At stop "
A9‑59
"
on
page 378
A9‑60 0xA93C Dead‑zone time 5 0 to 10000 1449 At stop "
A9‑60
"
on
page 378
A9‑61 0xA93D Dead‑zone time 6 0 to 10000 1661 At stop "
A9‑61
"
on
page 379
A9‑62 0xA93E Dead‑zone time 7 0 to 10000 1689 At stop "
A9‑62
"
on
page 379