6. Description of Parameters
- 136 -
6
Function Code Parameter Name Setting Range Default
F2-11
Torque limit source in speed
control (regenerative)
0: F2-10
1: AI
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication reference
6: Min. (AI1, AI2)
7: Max. (AI1, AI2)
8: F2-12
0
F2-12
Digital setting of torque
limit in speed control
regenerative)
0.0% to 200.0% 150.0%
This function parameter restricts output torque of the AC drive in speed control. The
torque limits are dened by F2-09 to F2-12.
When F2-11 is set to 0, the motoring state and regenerative state are not distinguished.
The torque limit is dened by F2-10.
When F2-11 is set to 1 to 8, the motoring state and regenerative state are distinguished.
In motoring state, full range of torque limit is set by F2-010. In regenerative state, full
range of torque limit is set by F2-12.
Figure 6-44 Torque limit in speed control
Forward run
Output torque
Reverse run
F2-12
F2-
12
F2-10
F2-10
Regenerative
Regenerative
Motoring
Motoring
Positive torque
Negative torque
Function Code Parameter Name Setting Range Default
F2-22
Regenerative power limit
selection
0: Disabled
1: Enabled in the whole
process
2: Enabled at constant
speed
3: Enabled during
deceleration
0
F2-23
Regenerative power limit 0.0% to 200.0% Model
dependent
In applications such as cam, quick acceleration/deceleration and sudden unloading
without using braking resistor, reduce bus voltage overshoot during motor braking so as
to prevent occurrence of overvoltage.
F2-23 is a percentage of rated motor power. If overvoltage still occurs after you set F2-22
=
1 , decrease setting of F2-23.