8. Peripherals and Options
- 241 -
● DIP switch setting
Table 8-11 Descriptions of DIP switch setting
Baud Rate Denition Address setting Denition DIP Switch
1 2 3 4 5 6 7 8
0 0 125Kbps 0 0 0 0 0 0 Reserved
ON
1 2 3
4 1
ON
ON
1 2 3 4
S2 S3
Baud
rate setting
CANopen
address setting
1 2 3 4 5 6 7 8
0 0 0 0 0 1 1
0 1 250Kbps 0 0 0 0 1 0 2
0 0 0 0 1 1 3
1 0 500Kbps ... …
1 1 1 1 0 1 61
1 1 1Mbps 1 1 1 1 1 0 62
1 1 1 1 1 1 63
● Indicators
Table 8-12 Descriptions of indicators
Indicator State Description
PWR (in red) ON Power-on is normal.
OFF Power-on is abnormal. Check whether the
installation is proper.
ERR (in red) ON The communication of the AC drive times out.
Flashing quickly The CANopen address is set incorrectly.
Flashing twice The CANopen messages emergently.
RUN (in green) ON The CANopen enters the "Operational" state.
Flashing The CANopen enters the "Pre-Operational" state.
OFF The CANopen enters the "Stopped" state.
CANopen
has the same bus topology and wiring method as CANlink
does.