8. Peripherals and Options
- 246 -
8
DIP switch setting
Probus-DP Communication Slave Address Setting Slave
Address
DIP Switch
1 2 3 4 5 6 7 8
Keep the
OFF state
(OFF:
MD38DP2).
0 0 0 0 0 0 0 Reserved
ON
1
2
3
4 5 6
7
8
S1
Reserved
DP slave
address setting
1 2 3 4 5 6 7 8
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 2
0 0 0 0 1 1 3
...
1 1 1 1 1 0 1 123
1 1 1 1 1 1 0 124
1 1 1 1 1 1 1 125
Indicators
Indicator Indication State Description
D4 in red Power supply
indicator
ON The drive is powered on.
OFF The drive is not powered on or DP card is installed
improperly.
D3 in yellow DP card
and master
communication
indicator
ON Communication between DP card and the master
is normal.
OFF There is no communication between DP card and
the master (check PROFIBUS cable connection
and setting of station No.).
Flash The master does not operate or error occurs on
communication between DP card and the master .
D2 in green DP card
and drive
communication
indicator
ON Communication between DP card and the drive is
normal.
OFF Communication between DP card and the drive
fails (check the baud rate setting).
Flash Interference exists on communication between DP
card and the drive or extension card address is
not within the rang of 1 to 125.