Appendix. Parameter Table
- 315 -
Parameter
No.
Parameter Name Setting Range Default Property Page
Group F6: Start/Stop Control
F6-00 Start mode 0: Direct start
1: Catching a spinning motor
2: Pre-excited start
3: SVC quick start
0
☆
1
1
7
F6-01 Mode of catching a spinning motor 0: From stop frequency
1: From zero speed
2: From max. frequency
0
★
1
1
7
F6-02 Speed of catching a spinning
motor
1 to 100 20
☆
1
1
7
F6-03 Start frequency 0.00 to 10.00 Hz 0.00 Hz
☆
1
1
7
F6-04 Start frequency holding time 0.0s to 100.0s 0.0s
★
1
1
7
F6-05 DC injection braking 1 level/Pre-
excitation level
0% to 100% 50%
★
1
1
7
F6-06 DC injection braking 1 active time
/Pre-excitation active time
0.0s to 100.0s 0.0s
★
1
1
7
F6-07 Acceleration/Deceleration mode 0 to 2 0
★
1
2
3
F6-08 Time proportion of S-curve start
segment
0.0% to (100.0% – F6-09) 30.0%
★
1
2
3
F6-09 Time proportion of S-curve end
segment
0.0% to (100.0% – F6-08) 30.0%
★
1
2
3
F6-10 Stop mode 0: Decelerate to stop
1: Coast to stop
0
☆
1
2
0
F6-11 DC injection braking 2 start
frequency
0.00 Hz to maximum
frequency
0.00 Hz
☆
1
2
0
F6-12 DC injection braking 2 delay time 0.0 to 100.0s 0.0s
☆
1
2
0
F6-13 DC injection braking 2 level 0% to 100% 50%
☆
1
2
0
F6-14 DC injection braking 2 active time 0.0s to 100.0s 0.0s
☆
1
2
0
F6-15 Braking use ratio 0% to 100% 100%
☆
-
F6-18 Catching a spinning motor current
limit
30% to 200% Model
dependent
★
-
F6-21 Demagnetization time (effective
for SVC)
0.00s to 5.00s Model
dependent
☆
-
F6-23 Overexcitation selection 0: Disabled
1: Enabled during
deceleration
2: Enabled in the whole
process
0
☆
-
F6-24 Overexcitation suppression
current level
0% to 150% 100%
☆
-
F6-25 Overexcitation gain 1.00 to 2.50 1.25
☆
-