MD500 User Manual 7. Description of Parameters
- 171 -
Ƶ
View Parameters in Group U0
You can view the parameter values by using operation panel, convenient for on-site commissioning, or from the host computer by
means of communication (address: 0x7000-0x7044).
8WR8DUHWKHPRQLWRULQJSDUDPHWHUVLQWKHUXQQLQJDQGVWRSVWDWHGHÀQHGE\)DQG)
Function Code Parameter Name Display Range
Group U0: Monitoring Parameters
U0-00 Running frequency 0.00 to 500.00 Hz
U0-01 Frequency reference 0.00 to 500.0 Hz
U0-02 Bus voltage 0.0 to 3000.0 V
U0-03 Output voltage 0 to 1140 V
U0-04 Output current WR$$&GULYHSRZHUN:
0.0 to 6553.5 A (AC drive power > 55 kW)
U0-05 Output power 0 to 32767
U0-06 Output torque -200.0% to 200.0%
Function Code Parameter Name Display Range
U0-07 DI state 0 to 32767
8,WGLVSOD\VWKHFXUUHQWVWDWHRI',WHUPLQDOV$IWHUWKHYDOXHLVFRQYHUWHGLQWRDELQDU\QXPEHUHDFKELWFRUUHVSRQGVWRD',´µ
LQGLFDWHVKLJKOHYHOVLJQDODQG´µLQGLFDWHVORZOHYHOVLJQDO7KHFRUUHVSRQGLQJUHODWLRQVKLSEHWZHHQELWVDQG',VLVGHVFULEHGLQ
the following table:
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8 %LW
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 ', DI10
Bit10 Bit11 Bit12 Bit13 Bit10 Bit11 Bit12 Bit13 Bit14 Bit15
VDI1 VDI2 VDI3 VDI4 VDI1 VDI2 VDI3 VDI4 VDI5 -
Function Code Parameter Name Display Range
U0-08 DO state 0 to 1023
U0-08: It displays the current state of DO terminals. After the value is converted into a binary number, each bit corresponds to a
DO. "1" indicates high level signal, and "0" indicates low level signal. The corresponding relationship between bits and DOs is
described in the following table.
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5
DO3 Relay 1 Relay 2 DO1 DO2 VDO1
Bit6 Bit7 Bit8 %LW Bit10 Bit11
VDO2 VDO3 VDO4 VDO5 - -
Function Code Parameter Name Display Range
U0-10 $,YROWDJH9FXUUHQWP$ 0.00 to 10.57 V
0.00 to 20.00 mA
U0-10: When F4-40 is set to 0, AI2 sampling data is displayed in the unit of V. When F4-40 is set to 1, AI2 sampling data is displayed
in the unit of mA.
Function Code Parameter Name Display Range
U0-14 Load speed display 0 to 65535
U0-15 PID reference 0 to 65535
U0-16 PID feedback 0 to 65535
U0-18 Pulse reference 0.00 to 100.00 kHz