7.10.5 Control of Digital Output (DO, Relay, FMR)
If a digital output terminal is allocated with the function 20: Communication setting, you can control the digital output by using the
host computer.
7KHFRPPXQLFDWLRQDGGUHVVDQGWKHFRPPDQGRIWKHGLJLWDORXWSXWVDUHGHÀQHGLQWKHIROORZLQJWDEOH
The related communication address and command are as follows:
Communication Address Command Description
2001H Bit0: DO1 output
Bit1: DO2 output
Bit2: Relay1 output
Bit3: Relay2 output
Bit4: FMR output
Bit5: VDO1
Bit6: VDO2
Bit7: VDO3
Bit8: VDO4
%LW9'2
7.10.6 Control of Analog and High-speed Pulse Output (AO, FMR)
When F5-06, F5-07 or F5-08 = 12, you can control the analog and high-speed pulse output by using the host computer.
7KHFRPPXQLFDWLRQDGGUHVVDQGWKHFRPPDQGRIWKHDQDORJDQGKLJKVSHHGSXOVHRXWSXWVDUHGHÀQHGLQWKHIROORZLQJWDEOH
The related communication address and command are as follows:
Communication Address Command Description
AO1 2002H 0 to 7FFF indicates 0% to 100%.
AO2 2003H
FMP 2004H
7.10.7 Parameter Initialization
You can initialize the parameters via the host computer by using this function. If FP-00 (user password) is set to a non-zero value,
verify the password on the host computer.
2QFHWKHSDVVZRUGSDVVHVWKHYHULÀFDWLRQWKHKRVWFRPSXWHUSHUIRUPVSDUDPHWHULQLWLDOL]DWLRQZLWKLQV7KHFRPPXQLFDWLRQ
DGGUHVVRIWKHSDVVZRUGYHULÀFDWLRQLV)+'LUHFWO\ZULWHWKHFRUUHFWXVHUSDVVZRUGWRWKLVDGGUHVVWRFRPSOHWHWKHYHULÀFDWLRQ
7KHFRPPXQLFDWLRQDGGUHVVDQGWKHFRPPDQGRIWKHSDUDPHWHULQLWLDOL]DWLRQDUHGHÀQHGLQWKHIROORZLQJWDEOH
Communication Address Command Description
1F01H 1: Restore factory parameters
2: Clear the records
4: Restore the user backup parameters
501: Back up the current user parameters